top of page
  • Writer's pictureKamino Energy

The latest Smart Grid stories

Updated: Jan 21, 2022

For all grid operators, the goal is to ensure that they operate a stable and reliable system, but this needs to be balanced against costs.


To achieve this, there needs to be a standard for an acceptable reliability level that can assure, with a high probability, that the voltage and frequency remain within an acceptable range.

That standard is the n-1 criteria. This always states that a system can tolerate an unexpected failure or outage of a single system component. This principle has achieved acceptable results over the past decades. This limit is calculated for each network. The actual figures vary from 50 to 70 per cent constant operation below the thermal threshold to ensure that the load in the transmission line does not exceed parameters. With this limit, you guarantee that whenever a fault or outage occurs, then the load in the remaining transmission line should not exceed more than 100 per cent of the thermal limit.

With the increased penetration of intermittent renewable generation and complexity to transmit this energy in dynamic situations that cannot be predicted, transmission lines can often violate this n-1 criterion. To maintain grid stability, it is vital that operators can manage this growing problem.

Avoiding the rising cost of redispatch The additional costs incurred in redispatch measures through compensatory payments passed through network usage charges from the TSOs to the end customers, making electricity more expensive.

According to the Federal Network Agency, the German regulatory office for electricity and gas, the share of network charges in the price of electricity for household customers in Germany rose from an average of 5.75 ct/kWh to 7.31 ct/kWh between 2011 and 2017. The economic damage caused by redispatch is enormous, with total costs of around €18 billion in 2017.

An effective way of solving the problem would be installing numerous reactive power compensation plants in the expanding electricity networks and building HVDC transmission lines from the generation centers to the load centers. However, expanding the network quickly enough to meet rising demand and renewable penetration is not feasible due to the high investment required and lengthy planning consent processes.

The other option would be to use conventional load flow controllers. So far, this has only been possible to a limited extent. Traditional load flow controllers can divide the transmission power between several lines reducing the need for current-related redispatch, but they are comparatively slow, and their ability to handle additional tasks such as harmonics for the AC network is limited. In power grids, phase shift transformers (PST) provide active power flow control. By enforcing or blocking loads, they improve the stability and flexibility of grids and help grid operators get the most out of existing hardware.

However, PSTs have slow response times and limited dynamic capability. They cannot provide reactive power compensation, so new technology is required. For decades, series compensation (SC) technology has improved grid stability and contributed to the optimal utilization of transmission lines. TSOs around the world have already benefited from solutions that were tailored to their specific requirements.

The main benefits of series compensation are the reduction of line voltage drops, limitation of load-dependent drops, and a reduction of the transmission angle. However, they have limited dynamic capabilities; large quantities are required to work effectively, and again they cannot provide reactive power compensation.

Unified power flow controller The optimum solution available would be to employ a dynamic load flow management solution such as UPFC (unified power flow controller). This is extremely fast to react and can manage both series and parallel compensation to keep lines within the n-1 criterion and the electricity flowing. The UPFC can balance load flow in the AC grid, rapidly bypass overloaded line sections, provide reactive power and dynamic voltage control, and utilize assets to physical limits without the need for safety margins.

Siemens Energy’s UPFC PLUS solution is based on the Modular Multilevel Converter (MMC) architecture that is already proven in the company’s SVC PLUS and HVDC PLUS technology. This UPFC is used to control and influence the transmitted electrical power in individual lines in national and meshed power grids. The system is designed for the high-voltage three-phase interconnections, such as the 380 kV and 220 kV voltage levels typical in Europe. It uses control power electronics like the technology used in HVDC, but in the case of UPFC, they are not used directly for power transmission, but for influencing and modulating the transmitted alternating current.

With a response time of 30ms, UPFC PLUS works significantly faster than a phase shifter, enabling appropriately rapid intervention in critical situations. Unlike a phase shifter, it can not only control the load flow but also offers the possibility of dynamic reactive power compensation and voltage control and can even dampen disturbances such as oscillations and harmonics.

4 views0 comments

Коментарі


bottom of page